Vector control optimisation
In general, the vector control is ready for operation after the motor parameters have been
identified. Vector control must only be optimised for the following drive performance:
Drive performance
Rough motor run and motor current (C0054) > 60 % rated motor
current in idle running (stationary operation)
Torque too low for frequencies f < 5 Hz (starting torque)
Poor constant speed at high loads (setpoint and motor speed are
not proportional).
Error messages OC1, OC3, OC4 or OC5 during acceleration times
(C0012) < 1 s (drive controller is no longer able to follow the
dynamic processes)
L
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Using the keypad XT EMZ9371BC − Vector control
Remedy
1. Reduction of motor inductance (C0092) by 10 %
2. Check of motor current under C0054
3. If the motor current (C0054) > 50 % rated motor current:
– C0092 must be reduced until the motor current amounts to
50 % of the rated motor current
– Reduce C0092 by max. 20 %!
Increase of motor resistance (C0084) or increase of motor
inductance (C0092)
Increase of slip compensation (C0021)
Overcompensation results in drive instability!
Change readjustment time of the I
Reduction of C0078 = I
l
dynamic)
l
Increase of C0078 = I
("smoother")
EDK82EV113 DE/EN/FR 8.1
7
Commissioning
−32−
controller (C0078):
max
controller becomes quicker (more
max
controller becomes slower
max
139