7
Commissioning
Using the keypad E82ZBC − Linear V/f characteristic control
Switch−on sequence
10.
Set the acceleration time T
(C0012)
ir
Lenze setting: 5.00 s
11.
Set the deceleration time T
(C0013)
if
Lenze setting: 5.00 s
12.
Set the V/f−rated frequency (C0015)
Lenze setting: 50.00 Hz
13.
Set the V
boost (C0016)
min
Lenze settings: Depending on the controller type
14.
If you want to change the settings, please go to
the menu
ALL
.
When you are ready with parameter setting:
15.
Setpoint selection
16.
Enable the controller.
17.
The drive should be running now at e.g. 30 Hz
124