3
Electrical installation
Mains connection 230 V/240 V
Fuses and cable cross−section (operation with rated power)
8200 vector
mains
Type
[kW]
E82EV302K2C
3.0
3/PE AC
E82EV402K2C
4.0
100 ... 264 V;
E82EV552K2C
5.5
45 ... 65 Hz
E82EV752K2C
7.5
8200 vector
mains
Type
[kW]
E82EV302K2C
3.0
3/PE AC
E82EV402K2C
4.0
100 ... 264 V;
E82EV552K2C
5.5
45 ... 65 Hz
E82EV752K2C
7.5
Fuse
E.l.c.b.
1)
Use UL−approved cables, fuses and fuse holders only.
UL fuse: voltage 240 V, tripping characteristic "H", "K5" or "CC"
2)
All−current sensitive e.l.c.b. for use with E82EVxxxK2C0xx
3)
All−current sensitive e.l.c.b. for use with E82EVxxxK2C2xx
4)
Flexible cable can only be connected using pin end connectors.
Observe national and regional regulations (e. g. VDE 0113, EN 60204)
100
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Operation without mains choke
Installation to EN 60204−1
Installation to UL
L1, L2, L3,
PE
2
[mm
]
M20 A
B20 A
4
20 A
M25 A
B25 A
4
25 A
4
M35 A
−
6
)
35 A
Operation only with mains choke
Operating with mains choke
Installation to EN 60204−1
Installation to UL
L1, L2, L3,
PE
2
[mm
]
M16 A
B16 A
2.5
15 A
M20 A
B20 A
4
20 A
M25 A
B25 A
4
25 A
4)
M35 A
−
6
35 A
EDK82EV113 DE/EN/FR 8.1
1)
L1, L2, L3,
FI
PE
[AWG]
12
³ 300 mA
10
2)
³ 30 mA
3)
8
1)
L1, L2, L3,
FI
PE
[AWG]
14
³ 300 mA
12
2)
³ 30 mA
3)
10
8
L