APPENDIX A: HORIZONTAL AND VERTICAL VENT CHART
For example, let's imagine an installation consisting of a horizontal
vent coming out at the back of the stove on a total distance of 8 feet.
This horizontal run is followed by a tee and a 6-foot vertical rise. This
type of installation is not acceptable. As you can see, the vent
termination is clearly outside the allowed configuration zone on the
chart because the venting system proposed does not have at least
one foot of vertical rise for each foot of horizontal run.
82
Stove Builder International Inc. | 48202 | Rev: May 31 2019 10:15AM | Uncontrolled Copy
(82 OF 91)
Possible Horizontal vent length (feet)
Cambridge II and Osburn 3000C Pellet Stove Installation and Operation Manual