5 MAINTENANCE
5.1 Trouble-shooting
In correct installation the transmitters are maintenance-free. If contamination or clogging
should occur during operation, the transmitter (paddle-wheel, bearing) can be cleaned with
water or another appropriate cleaning agent.
The message "ERROR" on the display indicates that calibration data has been lost. By
pressing ENTER, the user access to operation menu but the device works with the factory
settings (see §5.2). The transmitter must be re-calibrated. If this message appears more
often, please return the product to the factory.
5.2 Factory-settings of the 8025 at Delivery
Language:
English
Unit of flow:
L/s
Unit of totalizers: L
Decimal points:
2
K-factor:
46.60
Current: 4 mA:
00.00
20 mA: 03.00
Pulse output
unit: