Control Techniques Commander SE Guide D'utilisation page 51

Masquer les pouces Voir aussi pour Commander SE:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

PAd - Keypad reference selected. Terminals 10, 11, 12 and 13 do not have any
NOTE
function in this mode.
The settings for parameter 05 are explained fully on the following pages.
Parameter 5 set to A1.A2
Local voltage (A1) or remote current (A2) speed reference inputs
Input
Terminal 12 Terminal 13
Source
A1
open
A1
open
A2
closed
A2
closed
If the Run Forward and Run Reverse terminals are both closed, the drive will stop
NOTE
under the selected ramp and stopping modes.
Jog speed reference (parameter 15)
Terminal 12
Terminal 13
open or closed
closed
open or closed
closed
If jog speed is selected during normal running, the motor will accelerate or
NOTE
decelerate to the jog speed at the normal acceleration ramp (parameter 03) or
deceleration ramp (parameter 04) and then the jog acceleration and deceleration
ramps (0.2 seconds) will be selected. Once jog has been selected use the Run
Forward or Run Reverse terminals to jog.
Commander SE User Guide
Issue Number 9
Figure 6.3 Terminal connections
Enable
open
closed
open
closed
open
closed
open
closed
Enable
Run Forward
closed
closed
closed
www.controltechniques.com
Run Forward
Run Reverse
closed
open
open
closed
closed
open
open
closed
Run Reverse
open
open
closed
Motor Action
Run Forward
Run Reverse
Run Forward
Run Reverse
Motor Action
Jog Forward
Jog Reverse
51

Publicité

Table des Matières
loading

Table des Matières