If the drive is not mounted as indicated, hazardous live parts will be exposed and
the IP Rating or NEMA 1 enclosure rating of the drive will be invalid.
WARNING
Input phase
imbalance:
Ambient
temperature:
Storage temperature: -40°C to +60°C (-40°F to 140°F) for 12 months max
Altitude:
Humidity:
Materials:
Vibration (random):
Vibration
(sinusoidal)
Bump:
Frequency
accuracy:
Resolution:
Output frequency
range:
Starts per hour:
Power up delay:
18
Phase imbalance not to exceed 2% negative phase sequence
-10°C to +40°C (14°F to 104°F) at 6kHz switching frequency.
-10°C to +50°C (14°F to 122°F) at 3kHz switching frequency
with derating on some models.
-10°C to +40°C (14°F to 104°F) at 3kHz switching frequency for
SE4, 18.5kW and SE Size 5.
See Commander SE Advanced User Guide for Derating
Curves.
Reduce the normal full-load current by 1% for every 100m
(325ft) above 1000m (3250ft) to a maximum of 4000m
(13000ft).
Maximum relative humidity 95% (non-condensing)
Flammability rating of main enclosure:UL94-5VA (Size 1 to 4)
Flammability rating of main enclosure:UL94-V0 (Size 5)
Grommets:UL94-V1
Unpackaged - tested to 0.01g²/Hz (equivalent to 1.2g rms) from
5 to 150Hz for 1 hour in each of 3 axes in accordance with
IEC68-2-34 and IEC68-2-36.
Unpackaged - tested from 2-9Hz, 3.5mm displacement; 9-
2
200Hz 10m/s
acceleration; 200-500Hz, 15m/s
Duration - 15 minutes in each of 3 axes. Sweep rate 1 octave/
minute.
Test in accordance with IEC68-2-6.
Packaged - tested to 40g, 6ms, 100 times/direction for all 6
directions as in IEC68-2-29
Unpackaged - tested to 25g, 6ms, 100 times/direction for all 6
directions in accordance with IEC68-2-29
0.01%
0.1Hz
0 to 1000Hz
By using the electronic control terminals: Unlimited
By switching of the supply: 20 starts per hour maximum (3
minute intervals between starts)
1.5 seconds maximum (Allow at least 1 second for Sizes 1 to 4
and 1.5 seconds for Size 5 before monitoring the state of the
status relay contacts, communicating with the drive via serial
communications etc.)