AC Line reactor values
Drives used with
SE11200025, SE11200037
SE11200055, SE11200075,
SE2D200075, SE2D200110
SE2D200150, SE2D200220
SE23400075, SE23400110,
SE23400150
SE2D200075, SE2D200110,
SE2D200150, SE23400220,
SE23400300, SE23400400,
SE33400550, SE33400750
SE23200400, SE2D200220,
SE33200550, SE33200750
SE43401100, SE43401500
*SE43401850, *SE53402200
*SE53403000, *SE53403700
Commander SE sizes 3, 4 and 5 drives include DC chokes, AC reactors are only
NOTE
required for harmonic reduction.
*These input reactors are not stocked by Control Techniques. Therefore they
NOTE
should be ordered directly from the manufacturer, Skot Transformers, or sourced
locally.
sales@skot.co.uk
They can be ordered using the above part numbers or Skot reference numbers:
4400-0240 = 35232
4400-0241 = 35233
Line reactors also improve the input current waveform and reduce the input current
harmonic levels. Further information is included in the EMC Data sheet which is
available from Control Techniques' Drive Centres or Distributors.
4.4.5
Input line reactors for Harmonics standards EN61000-3-2 & IEC61000-3-2
The following input line reactors allow the Commander SE 0.25 - 0.55kW drives to
conform to harmonic standards EN61000-3-2 and IEC61000-3-2
Drive
SE12200025
SE12200037
SE12200055
EN61000-3-2 and IEC61000-3-2 applies to equipment with a supply voltage of 230Vac
and a line current up to 16A, single or three phase. Professional equipment with rated
input power exceeding 1kW has no limits - this applies to the 0.75kW drive.
Further information on EN61000-3-2 and IEC61000-3-2 is included on the EMC data
sheets available from your local Control Techniques Drive Centre or distributor.
4.4.6
Voltage fluctuation (Flicker) standard EN61000-3-3 (IEC61000-3-3)
Those models which fall within the scope of EN61000-3-3, as stated in the Declaration
of Conformity, conform to the requirements for manual switching, i.e. the voltage dip
32
Reactor
Input
part number
phases
1
4402-0224
1
4402-0225
1
4402-0226
3
4402-0227
3
4402-0228
3
4402-0229
3
4402-0232
3
4400-0240
3
4400-0241
Table 4.4 AC Line reactor values
Reactor
Power
part number
de-rating
4400-0239
None
4400-0238
None
4400-0237
18%
www.controltechniques.com
Inductance
Contin-
uous rms
current
mH
A
2.25
6.5
1.0
15.1
0.5
26.2
2.0
7.9
1.0
15.4
0.4
24.6
0.6
27.4
0.45
46
0.3
74
Input power Inductance
W
mH
374
4.5
553
9.75
715
16.25
Commander SE User Guide
Peak
Dimensions
current
(mm)
A
L
D
H
13
72
65
90
30.2
82
75
100
52.4
82
90
105
15.8
150
90
150
47.4
150
90
150
49.2
150
90
150
54.8
180 100 190
92
190 150 225
148
250 150 275
Continuous
rms current
2.4
3.2
4.5
Issue Number 9