* Following a drive trip and a reset via the Stop/Reset key the Run Forward or Run Reverse
terminals will need to be opened and closed to allow the drive to run. This ensures that the drive
does not start when the Stop/Reset key is pressed.
14
Voltage accuracy
Maximum output current
Protection
15
16
Function
Voltage rating
Current rating
Contact isolation
Update time
Operation of contact
Provide fuse or other over-current protection in status relay circuit.
WARNING
Commander SE User Guide
Issue Number 9
+24V output
Status relay (Normally open)
www.controltechniques.com
± 10%
100mA
tolerates continuous short circuit to 0V
Drive Healthy
240Vac /30Vdc
2A/6A (resistive)
2.5kVac (meets IEC664-1 with over voltage
category II)
6ms
OPEN - AC supply removed from drive
- AC supply applied to drive with the drive in a
tripped condition
CLOSED
- AC supply applied to drive with the drive in a
'ready to run' or 'running' condition (not tripped)