E.14
Menu item: Factory settings
MENU | SETTINGS | Installer level
FACTORY SETTINGS
Do you want to reset the settings?
F
Installer level menu structure (expanded and additional functions with control
module or system control)
F.1
Menu item: Noise reduction mode
MENU | SETTINGS | Installer level
Noise reduction mode
F.2
Menu item: Installation
MENU | SETTINGS | Installer level | Installation configuration
Installation
Autom. cooling:
Source regeneration:
Outdoor temp., 24 hr av.:
Cooling at outdoor temp.:
F.3
Menu item: Circuit
MENU | SETTINGS | Installer level | Installation configuration
Circuit
Set-back mode:
Cooling possible:
Min. cooling target flow temp.:
254
Yes, No
Set the time period for each day of the week, start and end time,
copy the settings for the day, Delete all time periods
When a heat pump is connected, the system control automatically
switches between heating mode and cooling mode.
Deactivated
Activated
Factory setting: Deactivated
The system control switches the Cooling function on and guides
the heat from the living room back to the earth via the heat pump.
Prerequisite:
–
The Automatic cooling function is activated
–
The Absence function is active.
On
Off
Factory setting: Off
Average value for the measured outdoor temperatures in the last
24 hours.
Cooling starts once the outdoor temperature (24-hour average)
exceeds the set temperature.
Factory setting: 15 °C
Eco: The heating function is switched off and the frost protection
function is activated. For outdoor temperatures that fall below 4 °C
for longer than four hours, the system control switches the heat
generator on and regulates to the set-back temperature: °C. At an
outdoor temperature above 4 °C, the system control switches the
heat generator off. The monitoring of the outdoor temperature re-
mains active. Heating circuit behaviour outside of the time periods.
Prerequisite:
–
Time-controlled is activated in the Heating → Mode function.
Normal: The heating function is switched on. The system control
regulates to the set-back temperature: °C. Prerequisite:
–
Time-controlled is activated in the Heating → Mode function.
Yes
No
Factory setting: No
The system control regulates the heating circuit to the min. cooling
target flow temperature: °C. Prerequisite: The Cooling possible:
function has been activated.
Installation and maintenance instructions 8000017440_FT