3.5
Application limits
The product works between a minimum and maximum
outdoor temperature. These outdoor temperatures define the
application limits for the heating mode, domestic hot water
mode and cooling mode. See technical data (→ Page 267).
Operating outside of the application limits leads to the
product switching off.
3.5.1
Heating mode
B
60
50
40
30
20
1
10
0
-30
-20
-10
0
A
Outdoor temperature
B
Heating water temperat-
ure
The minimal volume flow is 520 l/h in the start phase and
410 l/h in continuous operation.
3.5.2
DHW mode
B
60
50
40
30
20
1
10
0
-30
-20
-10
0
A
Outdoor temperature
B
Heating water temperat-
ure
The minimal volume flow is 520 l/h in the start phase and
410 l/h in continuous operation.
208
2
10
20
30
40
1
in the start phase
2
in continuous operation
2
10
20
30
40
50
1
in the start phase
2
in continuous operation
3.5.3
Cooling mode
B
25
20
15
10
5
5
10
15
A
Outdoor temperature
The minimal volume flow is 470 l/h in the start phase and
370 l/h in continuous operation.
3.6
Heating water minimum flow volume
A
Condition: SRC 720/2 system control or SR 940 control module installed,
or system without system control with electric back-up heater not derated
(or newer products), Minimal additional required heating water volume
(excluding the product's content volume) = 0 litres
For the thawing process of the outdoor unit's evaporator, it
is important that sufficient heat energy in the form of heating
water volume and minimum flow rate can be provided, see
the tables below. This can be guaranteed by using an on-site
bypass valve.
In order to have an additional heating water buffer volume
at your disposal and to increase the robustness of the sys-
tem, the system control should be installed in the living room
(control room). (→ Page 228)
Outdoor
Min. flow
unit out-
rate in l/h
put, elec-
tric back-up
heater activ-
ated, 5.4 kW
4 kW
410 l/h
6 kW
410 l/h
A
8 kW
690 l/h
Outdoor
Min. flow
unit out-
rate
put, elec-
tric back-up
heater de-
activated or
reduced
4 kW
410 l/h
6 kW
410 l/h
8 kW
690 l/h
Installation and maintenance instructions 8000017440_FT
20
25
30
35
40
B
Heating water temperat-
ure
Minimum heating water
volume in litres
Underfloor
Radiators
heating/fan
coils
0 l
0 l
0 l
Minimum heating water
volume
Underfloor
Radiators
heating/fan
coils
40 l
40 l
80 l
A
45
50