Call up MENU | SETTINGS | Installer level | Diagnostics
codes | 100 - 199 | D.124 Building circuit DHW conf..
The adjustment range is between 200 mbar and 900 mbar.
The heat pump operates at its optimum level when the nom-
inal flow can be achieved by setting the available pressure
(Delta T = 5 K).
9.2
Remaining feed head of the product
The remaining feed head cannot be set directly. You can
limit the remaining pump head in order to adjust the on-site
pressure loss in the heating circuit.
Call up MENU | SETTINGS | Installer level | Diagnostics
codes | 200 - 299 | D.231 Max. remaining feed head.
9.2.1
Heating circuit pump remaining feed head
1
2
3
4
B
900
800
700
600
500
400
300
200
100
0
0
200
400
600 800 1000 1200 1400
A
Volume flow (l/h)
B
Remaining feed head
[mbar]
1
10% PWM
2
20% PWM
3
30% PWM
4
40% PWM
9.2.2
Filling valve and stopcock pressure loss
B
120
100
80
60
40
20
0
0
500
1000
A
Volume flow (l/h)
8000017440_FT Installation and maintenance instructions
5
6
7
8
9
10
1600 1800
2000
5
50% PWM
6
60% PWM
7
70% PWM
8
80% PWM
9
90% PWM
10
100% PWM
1500
2000
2500
3000
B
Pressure loss (mbar)
9.3
Setting the min. and max. flow temperature
in heating mode (with no control connected)
1.
Call up MENU | SETTINGS | Installer level | In-
stallation configuration | Circuit | Min. target flow
temp.:or MENU | SETTINGS | Installer level | In-
stallation configuration | Circuit | Max. target flow
temp.:.
The display shows the minimum or maximum flow
temperature in heating mode.
2.
Change the flow temperature in heating mode and
confirm the change by pressing
Max. heating mode target flow temperature: 75 ℃
9.4
Instructing the end user
Danger!
Risk of death from legionella.
Legionella multiply at temperatures below
60 °C.
Ensure that the end user is familiar with
all of the Anti-legionella measures in order
to comply with the applicable regulations
regarding legionella prevention.
A
Explain to the end user how the safety devices work and
where they are located.
Inform the end user how to handle the product.
Draw particular attention to the safety warnings, which
the end user must follow.
Inform the end user that they must have the product
maintained in accordance with the specified intervals.
Explain to the end user how to check the system's water
volume/filling pressure.
Pass all of the instructions and documentation for the
product to the end user for safe-keeping.
10 Troubleshooting
10.1
Contacting your service partner
If you contact your service partner, please mention if pos-
sible:
The fault code that is displayed (F.xx)
The status code that is displayed by the product (S.xx)
10.2
Displaying the data overview (current sensor
A
values)
The data overview provides information on the display about
the current values for the product's sensors. These can be
called up via the menu.
Call up MENU | SETTINGS | Installer level | Data over-
view.
If you are in MENU | SETTINGS | Installer level | Test
modes | Actuator test, you can easily call up the data
overview by pressing
.
.
229