Error Messages; Error Messages In Manual And Automatic Operating Statuses; Error Messages While The X.tune Function Is Running - Burkert TopControl Basic 8694 Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7.6
Error messages
7.6.1
Error messages in MANUAL and AUTOMATIC operating
statuses
Display
Cause of fault
LED 1 (red)
Checksum error in data memory
on
→ Data memory defective
→ The device automatically switches to an older
Table 11:
Error messages in the operating statuses
7.6.2
Error messages while the X.TUNE function is running
Display
Cause of fault
LED 1 (red)
No compressed air connected
on
Compressed air failure while the X.TUNE
function was running
Actuator or control system deaeration side
leaking
Control system aeration side leaking
Table 12:
Error messages for the X.TUNE function
32
(possibly not current) data record.
english
Type 8694
Controlanddisplayelements
Remedial action
Not possible, device defective
Remedial action
Connect compressed air
Check compressed air supply
Not possible, device defective
Not possible, device defective