Manual mode

Using both keys, change the opening angle of the proportional valve from the
minimum value up to 100%.
Fig. 13: Manual mode
8.4

Set-up mode

Setting the minimum opening angle of the proportional valve
Fig. 14: Set-up mode
9

ERROR MESSAGES

Display
Cause
E.01
Sensor failure at the sensor input
(Pt 100)
E.02
Input current at the standard
signal input is outside the 4 and
20 mA range
E.03
The opening angle of the
proportional valve is greater than
95%
Table 2 Error messages
44
Increase the opening angle
Decrease the opening angle
Increase the opening angle
Decrease the opening angle
Remedy
Check the sensor
Check the standard signal
Type 8625