13.1.3 CHARACT -
Select the transfer characteristic between input signal
(position set-point value) and stroke
Characteristic (customer-specific characteristic)
This function can be used to activate a transfer characteristic with respect to set-point value (set-point position)
and valve stroke for correction of the flow-rate or operating characteristic.
The transfer characteristic can be changed via the communications software only.
Factory setting: DIP switch 3 set to OFF (linear)
DIP Switches Position
3
ON
OFF
Table 30:
DIP switch 3
The switching position of the DIP switches in the positioner has priority over the communications
software, i.e. settings of the correction characteristic (CHARACT) which are modified via the communica-
tions software are only active if DIP switch 3 in the positioner is set to ON.
Characteristics which can be selected via the communications software:
Characteristic
linear
1 : 25
1 : 33
1 : 50
25 : 1
33 : 1
55 : 1
FREE
Table 31:
Selection of characteristics
The characteristic type can be changed via the communications software only.
24)
64
Function
Correction characteristic for adjustment of the operating characteristic
(linearization of the process characteristic CHARACT)
Linear characteristic
Description
Linear characteristic
Equal percentage characteristic 1 : 25
Equal percentage characteristic 1 : 33
Equal percentage characteristic 1 : 50
Inversely equal percentage characteristic 25 : 1
Inversely equal percentage characteristic 33 : 1
Inversely equal percentage characteristic 55 : 1
User-defined characteristic, freely programmable via nodes
english
Type 8694