Burkert TopControl Basic 8694 Manuel D'utilisation page 49

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Type 8694
Electricalinstallation24VDC
Figure 38:
Connection of screw-type terminals
Connect the positioner according to the following tables:
Input signals from the control centre (e.g. PLC)
Terminal Configuration
4
Set-point value +
5
Set-point value GND
1
Binary input +
Table 18:
Assignment of screw-type terminals - input signals of the control center - cable gland
Output signals to the control center (e.g. PLC; for analog output option only)
Terminal Configuration
Analogue position feedback +
2
3
Analogue position feedback GND
Table 19:
Assignment of screw-type terminals - output signals to the control center - cable gland
Operating voltage
Terminal Configuration
6
Operating voltage +
7
Operating voltage GND
Table 20:
Assignment of screw-type terminals - operating voltage - cable gland
Option only
16)
1
2
16)
3
16)
4
5
6
7
External circuit
4
+ (0/4 ... 20 mA)
5
GND
1
+
with reference to terminal 7 (GND)
External circuit
2
+ (0/4 ... 20 mA)
3
GND
External circuit
6
24 V DC ± 10 %
max. residual ripple 10 %
7
english
0 ... 5 V
(log. 0)
10 ... 30 V (log. 1)
49

Publicité

Table des Matières
loading

Table des Matières