Type 8694
Pneumaticinstallation
Move actuator to end position
Turn the hand levers to the right using a screwdriver.
Note:
- do not press the hand levers when turning them
- observe the sequence as described below
→
1. Actuate hand lever pilot valve deaeration.
→
2. Actuate hand lever pilot valve aeration.
Both hand levers point to the right.
The actuator moves to the end position.
Figure 34:
Move actuator to end position
Move actuator back to the rest position
Turn the hand levers to the left using a screwdriver.
Note:
- do not press the hand levers when turning them
- observe the sequence as described below
→
1. Actuate hand lever pilot valve aeration.
→
2. Actuate hand lever pilot valve deaeration.
Both hand levers point to the left (normal position).
The actuator moves by spring force to the rest position.
Figure 35:
Move actuator back to the rest position
Caution:
If the pilot valves are actuated, electrical control is not possible.
▶ Move hand levers to normal position before starting up the device.