Télécharger Imprimer la page

Roger Technology EDGE1 Instructions Et Consignes Pour L'installateur page 72

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 122
Setting obstacle impact force sensitivity MOTOR 2
If the reaction time to obstacle impact force is too long, reduce the value of the parameter. If the impact force exerted
on obstacles is too high, reduce the value of parameter
N.B: repeat the acquisition procedure after any change made to this parameter.
Low motor torque:
= minimum obstacle impact force ...
N.B.: only use these settings if the medium motor torque values are not suitable for the installation.
Medium motor torque. Recommended setting for adjusting force settings correctly.
= minimum obstacle impact force ...
Maximum motor torque. May only be used if the gate is equipped with a sensing edge.
Setting motor torque MOTOR 2
Increasing or decreasing the value of the parameter increases or decreases motor torque and, as a result, adjusts
obstacle detection sensitivity.
Use values below
(strong winds or very cold temperatures).
The torque is set with parameter
Setting start acceleration MOTOR 1 during opening and closing
Setting start acceleration MOTOR 2 during opening and closing
01= the gate accelerates rapidly at start of manoeuvre ... 10= the gate accelerates slowly and progressively at start of
manoeuvre.
Enable electric lock release reverse impulse
Disabled.
Setting opening speed (%)
Setting closing speed (%)
minimum speed
SMARTY5 o 7
PARAMETER
Opening approach distance setting MOTOR1
Opening approach distance setting MOTOR2
Closing approach distance setting MOTOR1
Closing approach distance setting MOTOR2
from min.
to max.
automatically and it isn't adjustable.
Setting number of automatic closure attempts after activation of sensing edge or
obstacle detection (crush protection)
No automatic closure attempts.
From 1 to 3 automatic closure attempts. We recommend setting a value equal to or lower than the value set for param
eter
. Automatic closure is only performed if the gate is completely open.
Setting photocell mode during gate opening (FT1)
DISABLED. Photocell is not active or not installed.
STOP. The gate stops and remains stationary until the next command is received.
72
= maximum obstacle impact force
= maximum obstacle impact force.
SOLO ONLY for particularly lightweight installations not exposed to severe weather conditions
(reduced motor torque = increased sensitivity).
(increased motor torque = reduced sensitivity).
.
maximum speed.
Parameters visible ONLY if:
SMARTY7R
SMARTY5R5
ONLY IF
= SMARTY/EMA ENABLED
of turns performed by the motor at the minimum speed. Speed is setted by the control unit
(or
, if enabled:
different from
SMARTY4/HS
BE20/400
).
BR20/400/R

Publicité

loading