A PP (step mode) command activates the opening manoeuvre. With the gate fully open, automatic reclosure is exclu
ded. Another PP (step mode) command activates the closure manoeuvre.
A PED (partial opening) command activates the partial opening manoeuvre. Automatic reclosure is excluded. Another
PED (partial opening) command activates the closure manoeuvre.
Adjusting automatic closing time after partial opening
Pause time settable from 00 to 90 s.
Pause time settable from 2 to 9 min.
Adjusting opening delay (alignment) of MOTOR 2
During opening, MOTOR 2 starts with an adjustable delay after MOTOR 1.
From 0 to 10 s.
Adjusting closing delay (alignment) of MOTOR 1
During closing, MOTOR 1 starts with an adjustable delay after MOTOR 2.
From 0 to 30 s.
Setting reverse time after activation of sensing edge or obstacle detection
(crush prevention)
This sets the reverse manoeuvre time after activation of the sensing edge or the obstacle detection system.
From 0 to 60 s.
Electric lock mode selection
N.B.
red when gate is moving.
=0.5 seconds;
=1 second;
Enable electric lock
Disabled.
Enabled. When LEAF 1 approaches the gate closed stop, the controller delivers supplementary power to MOTOR 1 to
Enabled. When LEAF 1 approaches the gate closed stop, the controller delivers maximum power to MOTOR 1 to latch
Setting motor torque
Increasing or decreasing the value of the parameter increases or decreases motor torque and, as a result, adjusts
obstacle detection sensitivity.
Use values below
SOLO ONLY for particularly lightweight installations not exposed to severe weather conditions
(strong winds or very cold temperatures). In installations with gate leaves of different lengths, they torque value may
be set separately, setting a value for parameter
Setting obstacle impact force sensitivity MOTOR 1
If the reaction time to obstacle impact force is too long, reduce the value of the parameter. If the impact force exerted
on obstacles is too high, reduce the value of parameter
N.B: repeat the acquisition procedure after any change made to this parameter.
Low motor torque:
= minimum obstacle impact force ...
N.B.: only use these settings if the medium motor torque values are not suitable for the installation.
Medium motor torque. Recommended setting for adjusting force settings correctly.
= minimum obstacle impact force ...
Maximum motor torque. May only be used if the gate is equipped with a sensing edge.
.
=1.5 seconds.
between
and
(reduced motor torque = increased sensitivity).
(increased motor torque = reduced sensitivity).
.
= maximum obstacle impact force
= maximum obstacle impact force.
.
.