The bus coupler has the following electrical connections:
• IN socket (5): EtherCAT IN fieldbus input
• OUT socket (6): EtherCAT OUT fieldbus output
• X1S plug (7):
• 24 V DC power supply for bus coupler
• Ground screw (8): functional earth
The tightening torque for the connection plugs and sockets is 1.5 Nm +0.5.
The tightening torque for the M4x0.7 nut (SW7) on the ground screw is 1.25 Nm
+0.25.
Fieldbus connection
The IN (5) and OUT (6) fieldbus connections are designed as M12 sockets, fe-
male, 4-pin, D-coded.
See Table 4 for the pin assignments for the fieldbus connections. The view
u
shown displays the device connections.
Table 4: Pin assignments of the fieldbus connections
Pin
IN (5) and OUT (6) sockets
Pin 1
TD+
Pin 2
RD+
Pin 3
TD–
Pin 4
RD–
Housing
Ground (functional earth)
The controller can either be connected to fieldbus connection IN or OUT. Both
fieldbus connections are identical. However, we recommend connecting the
EtherCAT IN plug to the EtherCAT OUT plug of the upstream participant on all de-
vices.
Fieldbus cable
Danger caused by incorrectly assembled or damaged cables!
The bus coupler may be damaged.
Only use shielded and tested cables.
u
AVENTICS™ EtherCAT | R412018142-BAL-001-AH | English
5
IN
OUT
X1S
7
1
2
4
3
IN/OUT
NOTICE
Faulty wiring!
Faulty wiring can lead to malfunctions as well as damage to the network.
1. Comply with the EtherCAT specifications.
2. Only a cable that meets the fieldbus specifications as well as the connection
speed and length requirements should be used.
3. In order to assure both the protection class and the required strain relief,
the cable and plug assembly must be done professionally and in accor-
dance with the assembly instructions.
4. Make sure that you do not create a ring topology without a ring master.

Power supply

Electric shock due to incorrect power pack!
Danger of injury!
1. Only use the following power supply for the bus coupler:
- 24 V DC SELV or PELV circuits, each with a DC fuse that can interrupt a cur-
rent of 6.67 A within max. 120 s, or
- 24 V DC circuits meeting the requirements for energy-limited circuits as
described in section 9.4 of UL standard UL 61010-1, third edition, or
- 24 V DC circuits meeting the requirements for power-limited power
sources in accordance with section 2.5 of UL standard UL 60950-1, second
edition, or
- 24 V DC circuits meeting the requirements of NEC Class II in accordance
with UL standard UL 1310.
2. Make sure that the power supply of the power pack is always less than
300 V AC (outer conductor – neutral wire).
The X1S power supply connection (7) is an M12 plug, male, 4-pin, A-coded.
See Table 5 for the pin assignments for the power supply. The view shown dis-
u
plays the device connections.
7
Table 5: Power supply pin assignments
Pin
X1S plug
Pin 1
24 V DC sensor/electronics power supply (UL)
Pin 2
24 V DC actuator voltage (UA)
Pin 3
0 V DC sensor/electronics power supply (UL)
Pin 4
0 V DC actuator voltage (UA)
• The voltage tolerance for the electronic components is 24 V DC ±25%.
• The voltage tolerance for the actuator voltage is 24 V DC ±10%.
• The maximum current for both power supplies is 4 A.
• The power supplies are equipped with internal electrical isolation.
NOTICE
DANGER
2
1
3
4
X1S
27