3.2.5. Versions
The lifting unit is available in the following versions:
• Single-pump system with switchgear including main
switch
• Double-pump system with switchgear including main
switch
3.3.

Operating principle

The sewage that arrives is channelled into the collection reservoir
via the inlet pipes, where it collects.
If the water level rises as far as the switch-on level then the pump
is switched on by the integrated level control and the collected
sewage is pumped into the connected pressure pipe.
The pump is switched off when the switch-off level is reached and
the set follow-up time has elapsed.
When the high water level is reached, an acoustic warning is out-
put and there is a forced switch-on of all pumps. As soon as the
water drops below the high water level, the pumps are switched
off once the follow-up time has elapsed, and the warning mes-
sage is acknowledged automatically.
3.3.1. Special features of double-pump systems
• An automatic pump alteration occurs after every pump
operation.
• If one pump malfunctions, the other pump is automatically
used as the base-load pump.
• In the event of large volumes of sewage, both pumps can
be switched on in parallel.
3.4.

Operating modes

3.4.1. Operating mode S3 (intermittent operation)
This operating mode involves the maximum ratio between operat-
ing time and downtime:
S3 10%/120 s
operating time 12 s / downtime 108 s
3.4.2. Variant operating mode
Depending on the volume flow, the operating mode can vary
between S3 10%/120 s and S3 20%/120 s. For more precise infor-
mation, see the table in the appendix of these instructions.
3.5.

Technical data

For the technical data for the individual lifting units, see the table
in the appendix of these instructions.
3.6.

Type key

Salmson-Liftson
Example:
lix L2-10/EAD1-2-T0026-540-N/MS
Liftson
Sewage lifting unit
lix
Standard version
L
Size
1 = single-pump system
2
2 = Double-pump system
10
Maximum delivery head in m at Q = 0
Motor version
E
E = dry motor
R = reduced-power glanded motor
"Motor" material version
A
A = standard type
Seal version
D
D = 2 independent mechanical shaft seals
IE efficiency class, e.g.: 1 = IE1 (based on
1
IEC 60034-30)
-
not Ex-rated
2
Number of poles
Mains connection version
T
M = 1~
T = 3~
0026
/10 = rated power P
Frequency
5
5 = 50 Hz
6 = 60 Hz
40
Key for rated voltage
Additional electrical equipment
O = with bare cable end
N/MS
P = with plug
N/MS = with switchgear including main switch
3.7.

Scope of delivery

• Sewage lifting unit ready for connection with switchgear
and 4 m cable between motor and switchgear
• 1x inlet seal DN 100 for plastic pipe (Ø 110 mm)
• 1x keyhole saw (Ø 124 mm) for inlet DN 100
• 1x collar for inlet connection DN 50 (for separate intake or
for the suction line of the diaphragm hand pump)
• 1x collar for ventilation connection DN 70
• 1x flange connector DN 80/100 with flat gasket, collar,
pipe clamps, bolts and nuts for connecting the discharge
pipeline DN 100
• 1 set of fixation material (2 mounting brackets, screws,
wall plugs, washers)
• 6x (lix L1) or 8x (lix L2) damming protective strips for insu-
lation of structure-borne noise
• Installation and operating instructions for the lifting units
• Installation and operating instructions for the switchgear
3.8.

Accessories (optionally available)

• On pressure side:
• Flange connectors DN 80, DN 100, for connection of the
gate valve on the pressure side to the pressure pipe
• Gate valve DN 80 made of cast iron
• On intake side:
• DN 150 intake set comprising keyhole saw (Ø 175 mm)
and inlet seal
• Gate valves DN 100 and DN 150 made of PVC
• Inlet seal DN 100
• General:
• Diaphragm hand pump with R1½ connection (without
hose)
• 3-way cock for switching over to the manual suctioning
from the pump sump/tank
• Alarm switchgear
• Rechargeable battery (NiMH, 9 V, 200 mAh)
• Horn 230 V, 50 Hz
• Flash light 230 V, 50 Hz
34
in kW