9.4

Set safety position

Configuration option: Using the Bürkert Communicator
PC software or the display of the device (optional).
Display operation: Button functions
Select, activate
To adjust the safety position, switch to the "Parameters" detailed
view for position controllers.
How to switch to detailed view:
When using Bürkert Communicator for the configuration,
select
Position Controller
When using the display for the configuration, switch to
CONFIGURATION
on the home screen and select
Controller.
You are now in the "Parameters" detailed view.
How to configure the safety position:
Select SAFEPOS.
Select FUNCTION.
The following safety positions are available to choose from:
Valve tightly closed.
Close
Open
Valve opened.
34
Confirm
Back
in the navigation area.
Position
English
Type 3360, 3361
Start-up
User-defined
User-defined safety position.
The entry of the position in the user-defined
menu is described below.
Inactive
Valve remains in its current position.
Set safety position.
Entry of user-defined safety position (only if
safety position is selected).
Select Position.
Enter safety position
(0% = closed, 100% = open).
The safety position is now configured.
user-defined