Type 3360, 3361
Installing the valve
→
For devices with display module disconnect the connection
cable from the HMI interface.
2. Remove the LED and storage module:
Remove the LED and storage module:
Fastening
screws
Fastening screws
Metal housing
of LED and
storage module
Figure 14: Remove the LED and storage module and remove the actuator
cover
→
Remove 2 fastening screws (hexalobular-internal screws T20).
→
Grab the LED and storage module by both sides of the metal
housing and lift it out.
3. Removing actuator cover:
→
Loosen the 4 fastening screws (hexalobular-internal screws T25).
The screws are integrated securely in the actuator cover.
→
Remove the actuator cover.
The connection terminals are now accessible.
Removing actuator cover:
Actuator cover
8.3.3
Connecting the cable
→
Push the cable through the cable gland.
NOTE!
Take note for connection to spring-loaded terminals.
▶ Minimum length of wire ferrules: 8 mm
▶ Maximum cross-section of wire ferrules: 1.5 mm
(uncollared), 0.75 mm
(collared)
2
→
Strip at least 8 mm of insulation from the wires and crimp
ferrules on.
→
Attach the wires to the terminals. The terminal layout is provided
in the tables below from Page 29.
→
Tighten union nut of cable gland (tightening torque approx.
1.5 Nm).
NOTE!
The ingress of dirt or moisture may cause damage or
malfunction.
To preserve IP65 and IP67 protection, ensure the following:
▶ Unused cable glands must be sealed using dummy plugs.
▶ The union nuts of cable glands must be tightened. Tighten-
ing torque, dependent on the cable size or dummy plugs,
approx. 1.5 Nm.
English
2
27