Type 3360, 3361
Installing the valve
Use of set-point input 4...20 mA
If several Type 3360, 3361 devices are connected in series
and the electrical power supply for a device in this connected
series fails, the input of the failed device becomes highly
resistive. As a result, the 4...20 mA standard signal fails.
Choice of connection line:
When choosing the length and cross-section of the indi-
vidual wires, take into account the voltage drop in relation
to the maximum supply current.
8.1.1
Description of circular plug-in connectors
3
3
4
5
1
FE Functional earth
Figure 10: Circular plug-in connector, control valve
2
X3 – M12 circular plug,
5-pin
1
Operating voltage
5
4
2
X1 – M12 circular plug,
1
8-pin
8
Input and output signals
7
6
2
X2 – M12 socket, 5-pin
Input signals process
3
actual value
5
4
→
Connect the device in accordance with the tables.
8.1.2
X1 – M12 circular plug, 8-pin
Pin Wire colour* Layout (from device perspective)
Input signals from control centre (e.g. PLC)
Set-point value +
8
red
(0/4...20 mA or 0...5/10 V) for operating
voltage electrically isolated
7
blue
Set-point value –
1
white
Digital input +
Output signals to control centre (e.g. PLC) only required with
analogue output and/or digital output option
6
pink
Analogue output + (0/4...20 mA or 0...5/10 V)
5
grey
Analogue output –
4
yellow
Digital output 1 (24 V/0 V)
3
green
Digital output 2 (24 V/0 V)
2
brown
Digital inputs and digital outputs GND
* The specified wire colours refer to the connection cable, which is
available as an accessory with ID no. 919061.
Tab. 6:
X1 – M12 circular plug, 8-pin
English
0...5 V (log. 0)
10...30 V (log. 1)