Symbols for indicating device state in accordance with
NAMUR NE 107
If several device statuses exist simultaneously, the device status
with the highest priority is displayed.
Priority
Symbol
Description
Failure, error or fault!
Due to a malfunction in the device or its
peripherals, closed-loop control mode is
1
not possible.
→
Review the messages in the message
list.
Function check!
Work is being carried out on the device,
2
which means that closed-loop control
mode is temporarily not possible.
Outside specification!
The environment conditions or process
conditions for the device are not within
3
the specified range. Internal device diag-
nostics indicate problems within the
device or with the process properties.
Maintenance required!
The device is in closed-loop control
4
mode, but function will soon be restricted.
Perform device maintenance.
Tab. 19: Symbols in accordance with NAMUR NE 107
46
Symbols for displaying operating states
Priority Symbol Description
1
2
3
4
5
6
Tab. 20: Symbols for displaying operating states
English
Type 3360, 3361
Display operation (optional)
Device is no longer in closed-loop control
mode due to a severe error. The valve is
stuck in its position.
Energy pack active:
The supply voltage has been interrupted.
The device is supplied with power via the
energy pack.
In AUTOMATIC operating state the actuator
moves to the safety position (see symbol
"safety position")
In MANUAL operating state the actuator is
stuck in the last assumed position.
Device is in MANUAL operating state.
Device is in SIMULATION operating state.
The signal for the set-point value setting
default is simulated.
Process control active
Position control active