9.8
Configure process values
Configuration option:
Using the Bürkert Communicator PC software or the
display of the device (optional).
Display operation: Button functions
Select, activate
To configure process values, you to the "Parameters" detailed
view for inputs/outputs.
How to switch to detailed view:
→
When using Bürkert Communicator for the configuration,
select
in the navigation area.
Inputs/Outputs
→
When using the display for the configuration, switch to
CONFIGURATION
on the home screen and select
Outputs.
You are now in the "Parameters" detailed view.
9.8.1
Selecting and scaling standard signal for
process set-point value
How to select the standard signal for the process set-point
value:
→
Select SP/CMD.
→
Select ANALOG.type.
→
Select standard signal.
The standard signal for the process set-point value is now
selected.
38
Confirm
Back
Inputs/
English
Type 3360, 3361
Start-up
How to scale the process set-point value:
→
Select SP.scale.
→
Enter the minimum and maximum values.
The process set-point value is now configured.
9.8.2
Selecting and scaling standard signal for
process actual value
How to select the standard signal for the process actual value:
→
Select PV.
→
Select ANALOG.type.
→
Select standard signal.
The standard signal for the process actual value is now
selected.
How to scale the process actual value:
→
Select PV.scale.
→
Enter the minimum and maximum values.
The process actual value is now configured.