Type 3360, 3361
Installing the valve
8.3.5
Terminal layout – input signal from control
centre (e.g. PLC)
Clip
Layout (from device perspective)
8
Set-point value +
(0/4...20 mA or 0...5/10 V)
for operating voltage electrically isolated
7
Set-point value –
5
Digital input +
Digital input GND
4
relates to GND operating voltage (GND Clip)
Tab. 11: Terminal layout – input signal from control centre (e.g. PLC)
8.3.6
Terminal layout – output signals to control
centre (e.g. PLC) only required with
analogue output and/or digital output
option
Clip
Layout (from device perspective)
Analogue output +
19
(0/4...20 mA or 0...5/10 V)
20
Analogue output –
18
Digital output 1 (24 V/0 V)
17
Digital output 2 (24 V/0 V)
16
Digital output GND
Tab. 12: Terminal layout – output signal to control centre (e.g. PLC)
0...5 V (log. 0)
10...30 V (log. 1)
8.3.7
Terminal layout – process actual value
input (only with process control function)
Signal
Clip
Assignment
type*
4...20 mA
22
+24 V supply
- internally
transmitter
supplied
15
PV1: not used
21
GND
(identical to GND oper-
ating voltage)
14
PV2: output from
transmitter
13
PV3: Bridge to GND
(GND from 3-wire
transmitter)
4...20 mA
22
not used
- externally
15
not used
supplied
21
not used
14
PV2: Process actual +
13
PV3: Process actual –
Frequency
22
+24 V supply sensor
- internally
supplied
15
PV1: Cycle input +
21
GND
14
PV2: not used
13
PV3: Bridge to GND
(GND from 3-wire
transmitter)
English
Device
External circuit
end
22
Transmitter
15
GND
21
I
14
13
14
4...20 mA
13
GND 4...20 mA
22
+24 V
15
Cycle +
21
GND (identical to
GND operating
voltage)
13
Cycle –
29