Installation et démarrage de l'ASI KEOR XPE
4.5.1.5 Battery switch auxiliary contact
Auxiliary contact of the battery switch; terminals X10-9/10.
➢ Single battery configuration: this auxiliary input must have a bridge.
➢ Distributed battery configuration: this input must be connected to the auxiliary
contact of the battery switch (BCB) if external. If not present, bridge this auxiliary
input.
4.5.1.6 Auxiliary contact of the diesel generator
Auxiliary contact coming from a generator set; terminals X10-11/12.
A normally open contact must be used; the contact must close when the
diesel generator is working properly.
The micro-processor acquires the contact status and, on restart of the rectifier, enables the
"Diesel Mode", operating at reduced DC voltage to reduce the
absorbed power. This contact can only be used in the event of a distributed battery.
Installation and start-up of KEOR XPE UPS