Télécharger Imprimer la page

Battery Switch Auxiliary Contact; Auxiliary Contact Of The Diesel Generator - LEGRAND KEOR XPE Serie Manuel De Fonctionnement

Masquer les pouces Voir aussi pour KEOR XPE Serie:

Publicité

Les langues disponibles

Les langues disponibles

Installation et démarrage de l'ASI KEOR XPE

4.5.1.5 Battery switch auxiliary contact

Auxiliary contact of the battery switch; terminals X10-9/10.
➢ Single battery configuration: this auxiliary input must have a bridge.
➢ Distributed battery configuration: this input must be connected to the auxiliary
contact of the battery switch (BCB) if external. If not present, bridge this auxiliary
input.

4.5.1.6 Auxiliary contact of the diesel generator

Auxiliary contact coming from a generator set; terminals X10-11/12.
A normally open contact must be used; the contact must close when the
diesel generator is working properly.
The micro-processor acquires the contact status and, on restart of the rectifier, enables the
"Diesel Mode", operating at reduced DC voltage to reduce the
absorbed power. This contact can only be used in the event of a distributed battery.
Installation and start-up of KEOR XPE UPS
Installazione e avviamento KEOR XPE UPS
OMAF9212 REV. A
55

Publicité

Chapitres

loading