Alarm
Description
Possible
causes
Solutions
Alarm
Description
Possible
causes
Solutions
Alarm
Description
Possible
causes
Solutions
Alarm
Description
Possible
causes
Solutions
78
OMAF9213 REV. A
KEOR XPE UPS user manual
Manuel de l'utilisateur de l'ASI KEOR XPE
Utilizzo dell'UPS KEOR XPE
AS44
BCBS OPEN
The system battery switch is open.
➢ The system battery switch open.
1. Check the status of the battery system switch.
2. Check the switch auxiliary contact is working.
3. Check the connection between the auxiliary contact of the isolator
and the auxiliary terminals of the IOBM.
4. If the alarm persists, contact our technical support service.
AS45
BMS BATTERY ALARM
battery <-
Presence of alarms in the BMS of the lithium battery (if lithium battery
present with BMS).
➢ The BMS of the lithium battery is in error status.
1. Contact the technical support service.
AS46
LOST OF REDUNDANCY
The continuity of the power supply is not guaranteed in the event of a
fault on one of the Power Units.
➢ The total load is over the expected maximum value.
➢ Measuring circuit failure.
1. Check the load supplied by the system.
2. If the alarm persists, contact our technical support service.
AS47
PEAK BATTERY OVERCURRENT
At least one Power Unit has enabled alarm
A47 PEAK BATTERY OVERCURRENT.
➢ Refer to alarm A47 PEAK BATTERY OVERCURRENT
of the Power Unit.
1. Refer to alarm A47 PEAK BATTERY OVERCURRENT
of the Power Unit.
-> only for config. single battery <-
-> only for config. single