3.3.2 Minimum distances from the walls and ventilation

For the dimensions, consult the technical documentation relating to the system.
Figure 15 - Distances to meet
The UPS must be installed to guarantee its inspection possibilities and promote the correct air
flow as much as feasibly possible.
For all dimensions of UPS, the same installation conditions apply regarding the minimum
distances from the walls, as indicated in the following tables.
If the POWER UNITS can be moved using a forklift, the minimum distances from the walls are
outlined in the table.
Recommended distances
Minimum distances
If the POWER UNITS can be moved only using a pallet truck, the minimum distances from the
walls are outlined in the table.
Recommended distances
Minimum distances
The following table displays the air volume requested for optimal ventilation and cooling of the
device. The values refer to dual conversion operation on-line with a nominal load.
Power (kVA)
3
Air volume (m
/h)
36
OMAF9212 REV. A
Installation and start-up of KEOR XPE UPS
Installation et démarrage de l'ASI KEOR XPE
Installazione e avviamento KEOR XPE UPS
A (mm)
50
0
A (mm)
600
600
750
900
6600
6900
B (mm)
C (mm)
1200
50
1200
0
B (mm)
C (mm)
1200
50
1200
0
1000
1200
1500
8800
9200
11500
D (mm)
600
400
D (mm)
600
400
1800
2100
13800
16100