The following information is displayed:
• Parallel type
The string can have the values, "POWER", "REDUNDANT+X", "AUTO".
➢ POWER means the parallel system is set to need the presence of all the UPS to
power the load.
➢ REDUNDANT+X means the system is redundant and the redundancy index is
indicated by the number "X". For example, in a system composed of 3 Power
Units, "REDUNDANT+2" means that just one of the Power Units is sufficient to
power the load.
➢ AUTO means that redundancy is calculated automatically by the system based
on the load outbound.
• Power Unit Number
The number represents the number of Power Units on the system
• Inv system status / Rect system status (communication bus control)
This field is a general indication of communication between the Power Units and the IOBM
of the system.
➢ The numbers indicate the communication slots available of the system.
➢ The letters M and S respectively stand for MASTER and SLAVE.
➢ The brackets [ ] indicate the position of the IOBM on the system.
➢ A possible question mark alongside a number indicates that Power Unit is not
communicating on the data bus.
We can assume we have the following situation:
➢ the system composed of 4 Power Units and an IOBM, the slots 6, 7, 8 are free;
➢ at the moment, the MASTER Power Unit is Power Unit 2;
➢ the IOBM has index 5;
➢ the Power Unit 4 is not communicating.
The page is presented as shown below.
Figure 41 – INFO section – PARALLEL - inv parallel bus communication status (System)
• Messages statistics
The statistics section relating to the messages exchanged on the communication buses is
composed of four different parts.
➢ STAT CAN SSW → Number of messages received and accuracy percentage
of receipt, relating to the static switches status.
➢ STAT CAN INVERTER→ Number of messages received and accuracy
percentage of receipt, relating to the system inverters status.
52
OMAF9213 REV. A
KEOR XPE UPS user manual