LEGRAND KEOR XPE Serie Manuel De Fonctionnement page 284

Masquer les pouces Voir aussi pour KEOR XPE Serie:

Publicité

Les langues disponibles

Les langues disponibles

Status
Description
Working
condition
Status
Description
Working
condition
Status
Description
Working
condition
Status
Description
Working
condition
Status
Description
Working
condition
Status
Description
Working
condition
Status
Description
Working
condition
66
OMAF9213 REV. A
KEOR XPE UPS user manual
Manuel de l'utilisateur de l'ASI KEOR XPE
Utilizzo dell'UPS KEOR XPE
SS8
INVERTER MASTER SYNCHRONIZED
The inverter is synchronised with the MASTER.
This status is present only on the SLAVE Power Unit and indicates the
inverter is synchronised with the signal sent from the MASTER.
SS13
BATTERY CHARGE
The battery is charging.
The static switch of the battery is closed and the battery is charging.
SS14
BATTERY CHARGE I
The battery is charging.
The static switch of the battery is closed and the battery is in the first I/O
charging phase (DIN 41773), with constant current and increasing
voltage.
SS15
BATTERY CHARGE U
The cyclic charge of the battery is enabled.
The static switch of the battery is closed and the battery is in the second
and final I/O charging phase (DIN 41773), with voltage current and
decreasing current.
SS16
HIGH BYPASS COMMUTATION
Switching with bypass high voltage.
Switching from inverter to bypass with inverter switch off caused by
bypass voltage over or equal to 10% of the bypass rated voltage.
SS18
EXTERNAL SYNC INVERTER SYNCHR.
The inverters are synchronised with the external synchronisation signal.
The status is active when the inverters are synchronised with the
external synchronisation signal.
SS19
EXTERNAL SYNC INHIBITED
Acquisition of the external synchronisation signal is disabled.
The synchronisation signal was manually inhibited using the specific
display menu.