Alarm
AS39
Description
The fuses of the bypass capacitors are not connected.
➢ Fuses broken on the bypass condensers.
Possible
causes
➢ The FCU fuse box is open.
Solutions
1. Check and reposition, if necessary, the fuses in the FCU fuse box.
2. Check the connection between the auxiliary contact of the FCU
3. If the alarm persists, contact our technical support service.
Alarm
AS40
Description
At least one Power Unit has enabled alarm A40 MINIMUM DC
VOLTAGE.
➢ Refer to alarm A40 MINIMUM DC VOLTAGE of the Power Unit.
Possible
causes
Solutions
1. Refer to alarm A40 MINIMUM DC VOLTAGE of the Power Unit.
Alarm
AS41
Description
At least one Power Unit has enabled alarm
A41 MAX DC BATTERY CURRENT.
➢ Refer to alarm A41 MAX DC BATTERY CURRENT
Possible
causes
Solutions
1. Refer to alarm A41 MAX DC BATTERY CURRENT
Alarm
AS42
Description
Parallel cable redundancy loss.
➢ One of the parallel cables is disconnected.
Possible
causes
Solutions
1. Contact the technical support service.
Alarm
AS43
Description
At least one Power Unit has enabled alarm A43 MAX LOAD CURRENT.
➢ Refer to alarm A43 MAX LOAD CURRENT of the Power Unit.
Possible
causes
Solutions
1. Refer to alarm A43 MAX LOAD CURRENT of the Power Unit.
KEOR XPE UPS user manual
Utilizzo dell'UPS KEOR XPE
BYPASS CAP FUSES BLOWN
fuse box and the CPU of the UPS.
MINIMUM DC VOLTAGE
MAX DC BATTERY CURRENT
of the Power Unit.
of the Power Unit.
PARALLEL CABLE REDUNDANT
MAX LOAD CURRENT