Instructions for assembly and use
Fault
number
-5
No operating unit connected.
Operating unit no longer
-10
connected after at least one was
recognised during launch.
-21
Heater temperature sensor broken. Defective temperature sensor or poor contact.
Heater temperature sensor short-
-22
circuiting.
-24
Bench temperature sensor broken.
Bench temperature sensor short
-25
circuit.
-26
Humidity sensor broken.
-27
Humidity sensor short-circuiting.
-30
Thermal fuse defective.

3.16.0 VERSION DISPLAY

By simultaneously pressing the
version number of the power unit is displayed on the operating unit for 3 seconds. The number
"14" appears on the 7 segment display of the operating unit, for example.
If you press the
operating unit is displayed with a preceding "P" (for panel), to distinguish it from the base unit, e.g.
"P14".
When the time has elapsed, the display reverts to stand-by mode.
WE DO IT FIRST.
Description
,
key again during this time, the software version number of the
Rectification/cause
No operating unit connected or poor contact.
Verify contact to operating unit.
Defective temperature sensor or short circuit.
Defective temperature sensor or poor contact.
Defective temperature sensor or short circuit.
Defective humidity sensor or poorly/wrongly
connected.
Defective humidity sensor, poorly/wrongly
connected or short circuit.
Defective heater sensor, poor contact or thermal
fuse not connected.
Inform service!
and
keys in stand-by mode, the software
36 /228