Electric wire rope winch BETA EL
English
4.2 Indication EMV
The electric wire rope winch with control is designed for industry.
The winch has to be switched at max. 5 times/minute to accomplish the standards for electromagnetic
emissions EN DIN 50081-2).
EMV proceedings (filter) have to be carried out if the winch has to be switched more than 5 times/mi-
nute or by using other electronic switching circuits (on site or delivered as option).
4.3 Connection to three-phase network
The connecting plan integrated in the motor terminal box has to be observed.
4.3.1
Motor-connection-Junction plate, three-phase current, 1 speed
Star connection
Y
Delta connection
4.3.2
Motor-connection-Junction plate, three-phase current, 1 speed, UL-R (CSA) NEMA
230 V
460 V
technische Änderungen vorbehalten
W2
U2
V2
U1
V1
W1
L1
L2
L3
W2
U2
V2
U1
V1
W1
L1
L2
L3
design changes under reserve
04.01.401
f = 50 Hz:
driving power < 3,0 kW
voltage: 380 ÷ 420 V
f = 60 Hz:
driving power > 3,6 kW
voltage: 440 ÷ 460 V
f = 50 Hz:
driving power < 3,0 kW
voltage: 380 ÷ 420 V
f = 60 Hz:
driving power > 3,6 kW
voltage: 440 ÷ 460 V