Siemens SINAMICS G120 Mode D'emploi page 753

Masquer les pouces Voir aussi pour SINAMICS G120:
Table des Matières

Publicité

Power module
T_max heatsink
Temperature measurement
Pulse freq setp
0.500 ... 16.000 [kHz]
p1800 [D] (4.000)
I_act abs val [Arms]
r0068
[0]
[6714.8]
i²t model
power
module
PU PI_rated [Arms]
r0207[0..4]
1
2
Signals and monitoring functions
Thermal monitoring, power module
Control Unit
Maximum power module temperature
Max
Min
PM temperatures [°C]
r0037 [0..19]
PM overload I2t [%]
r0036
3
4
Thermal monitoring for the power module
1
1
Faults "Power unit overtemperature"
F30004 "Overtemperature heat sink AC inverter"
0
F30024 "Overtemperature thermal model"
F30025 "Chip overtemperature"
F30035 "Air intake overtemperature"
F30068 "Undertemperature inverter heat sink"
PU T_alrm thresh
0 ... 25 [°C]
p0292 (5)
+
1
Alarms "Power unit overtemperature"
A05000 "Overtemperature heat sink AC inverter"
0
A05001 "Overtemperature depletion layer chip"
A05002 "Air intake overtemperature"
A05006 "Overtemperature thermal model"
100 %
1
F30005 "Power unit: Overload I2t"
0
1
PU I2t alrm thresh
10.0 ... 100.0 [%]
p0294 (95.0)
1
A07805 "Power unit overload I2t"
0
5
6
fp_8021_97_51.vsd
13.03.2018
V4.7_10
ZSW fault/alarm 2
r2135
r2135
.13
[2548.2]
1 = Fault power unit
thermal overload
ZSW fault/alarm 2
r2135
r2135
.15
[2548.2]
1 = Alarm power unit
thermal overload
Overload response
PU overld response
0 ... 13
p0290 (2)
7
8
Function diagram
- 8021 -
G120 CU230P-2

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Cu230p-2Cu230p-2 hvacCu230p-2 btCu230p-2 dpCu230p-2 pnCu230p-2 can