Internal control/status words
Status word 1 (r0052)
Bit No.
ZSW seq_ctrl
.0
0
1 = Ready for switch on
ZSW seq_ctrl
.1
1
1 = Ready (DC link loaded, pulses inhibited)
ZSW seq_ctrl
.2
2
1 = Operation enabled
ZSW fault/alarm 1
.3
3
1 = Fault present (pulses inhibited)
ZSW seq_ctrl
.4
4
1 = No coast down active (OFF2 inactive)
ZSW seq_ctrl
.5
5
1 = No Quick stop active (OFF3 inactive)
ZSW seq_ctrl
.6
6
1 = Switching on inhibited active
ZSW fault/alarm 1
.7
7
1 = Alarm present
ZSW monitor 1
.7
8
1 = No deviation setpoint/actual speed
ZSW seq_ctrl
.7
9
1 = Control request
1 = Maximum speed reached (f_act • p1082 (f_max))
ZSW monitor 1
.6
10
0 = f_act < p1082 (f_max)
ZSW cl-loop ctrl
.13
11
0 = I,M,P limit reached
Reserved
12
ZSW fault/alarm 2
.14
13
0 = Alarm motor overtemperature
ZSW monitor 1
.3
14
1 = Motor rotates forwards
ZSW fault/alarm 2
.15
15
0 = Alarm drive converter overload
3
4
Status word 1 (r0052)
<1>
5
6
fp_2510_97_01.vsd
13.03.2018
V4.7_10
ZSW 1
r0052
r0052
r0052.0
r0052.1
r0052.2
Signal is inverted if connected to a Digital
r0052.3
Output.
r0052.4
r0052.5
r0052.6
r0052.7
r0052.8
r0052.9
r0052.10
r0052.11
r0052.13
r0052.14
r0052.15
7
8
Function diagram
- 2510 -
G120 CU230P-2