In order to maintain the PROFIdrive profile, receive word 1 must be used as control word (STW1)
(due to bit 10 "control requested").
<2>
Using the connector-binector converters, the bits can be extracted from two of the PZD receive words 3 to 8 and used as binectors.
<3>
The following representation applies for words: 4000 hex = 100 %.
The reference variables p200x apply for the ongoing interconnection (100 % -> p200x).
The following applies for temperature values: 100 °C -> 100 % = 4000 hex, 0 °C -> 0 %.
<4>
Every PZD word can be assigned a word or a double word. Only one of the 2 interconnection parameters r2050 or r2060 can have a value <> 0 for a PZD word.
<5>
When interconnecting a connector output multiple times all the connector inputs must have either Integer or FloatingPoint data type.