Ramp-function generator selection
n_set_5
[3070.8]
From the extended ramp-function generator
ZSW n_ctrl
r1407
[2522.7]
r1407
.7
1 = Torque limit reached
<1>
Behavior of the response ramp of the torque limiting:
p1145 = 0.0: No ramp-function generator tracking. The ramp-function generator ramp is no longer in the range of the speed actual value.
p1145 = 1.0: The ramp-function generator ramp remains as close as possible to the speed actual value.
p1145 > 1.0: The ramp-function generator ramp is steeper than for p1145 = 1.0 (higher "speed following error").
<2>
For p1145 > 0, ramp-function generator tracking is activated when the torque limiting responds. This means that the speed
controller output only exceeds the torque limit by a deviation that can be set via p1145.
1
2
Setpoint channel
Ramp-function generator selection, status word, tracking
RFG track intens
0.0 ... 50.0
p1145 [D] (0.0)
<1>
3
4
x,y
x
T1
y
x
t
Interpolator
Ramp-function generator tracking
Ramp-function generator status word
Bit
Hochlaufgeber-Zustandswort
[3070.8]
0
Ramp-up active
Ramp-down active
[3070.8]
1
2
Ramp-function generator active
1
3
Ramp-function generator set
Ramp-function generator held
4
[3080.8]
5
Ramp-function generator tracking active
Maximum limiting active
[3050.8]
6
7
Ramp-function generator acceleration positive
Ramp-function generator acceleration negative
8
9
Reserved
10
Reserved
Reserved
11
12
Reserved
Reserved
13
14
Reserved
Reserved
15
5
6
fp_3080_97_01.vsd
13.03.2018
V4.7_10
Speed setpoint sum [rpm]
r1170
[3050.1]
[6030.1]
[6822.1]
[8011.1]
Ramp flattening-off
[3070.3]
RFG ZSW
r1199
r1199
.5
RFG ZSW
r1199
r1199
r1199.2
(p2148)
<2>
7
8
Function diagram
- 3080 -