Bit No.
Missing enable signals (r0046)
0
1 = OFF1 enable missing
1 = OFF2 enable missing
1
2
1 = OFF3 enable missing
1 = Operation enable missing
3
4
1 = DC current brake, enable missing
...
Reserved
1 = Safety enable missing
8
...
Reserved
10
1 = Ramp-function generator enable missing
1 = Ramp-function generator start missing
11
12
1 = Setpoint enable missing
Reserved
...
16
1 = OFF1 enable internal missing
17
1 = OFF2 enable internal missing
1 = OFF3 enable internal missing
18
19
1 = Pulse enable internal missing
1 = DC current brake, internal enable missing
20
21
1 = PU enable missing
...
Reserved
25
1 = Function Bypass active
26
1 = Drive inactive or not operational
27
1 = Demagnetizing not completed
Reserved
...
30
1 = Speed controller inhibited
1 = Jog setpoint active
31
1
2
Internal control/status words
Sequence control - Missing enable signals, line contactor control
Missing enable sig
r0046
r0046
r0046.0
r0046.1
r0046.2
Fault with OFF3 response
r0046.3
r0046.4
r0046.8
r0046.10
Close main cont
p0870
r0046.11
r0046.12
[2610.4]
Line contactor control
r0046.16
from sequence control
r0046.17
r0046.18
r0046.19
r0046.20
r0046.21
r0046.25
r0046.26
r0046.27
r0046.30
r0046.31
3
4
2000.00 µs
Control Unit
[3020.5]
0 = Internal quick stop
[3070.1]
1
[3070.4]
1 = Internal RFG enable
1
[3070.1]
Energize line
(0)
contactor
1
r0863.1
[2242]
Line contact feedb
p0860
(863.1)
[2221]
ON/OFF monitoring
LineContact t_mon
p0861
F07300 "Line
T
0
contactor
1
feedback signal
missing"
Time monitoring
Operating monitoring
&
&
5
6
Function diagram
fp_2634_97_01.vsd
G120 CU230P-2
13.03.2018
V4.7_10
Line supply
DO
+24 V
DI
Converter
7
8
- 2634 -