Siemens SINAMICS G120 Mode D'emploi page 740

Masquer les pouces Voir aussi pour SINAMICS G120:
Table des Matières

Publicité

Tec_ctr mop config
p2230 [D] (0000 0100 bin)
0
1
2
Non-volatile data save active
3
Ramp-function generator is always active
4
Tec_ctrl mop raise
p2235 [C]
(0)
Tec_ctrl mop lower
p2236 [C]
(0)
Tec_ctrl mop max
-200.00 ... 200.00 [%]
p2237 [D] (100.00)
Tec_ctrl mop min
-200.00 ... 200.00 [%]
p2238 [D] (-100.00)
<1>
For p2230.0 = 0, this setpoint is entered after ON.
<2>
If initial rounding-off is active (p2230.2 = 1), the selected ramp-up/down times are exceeded accordingly.
1
2
Technology controller
Motorized potentiometer
Data save active
0
The setpoint for the motorized potentiometer is not saved and after ON is entered using p2240.
1
The setpoint for the motorized potentiometer is saved after OFF and after ON is entered using r2231.
Initial rounding-off active
0
Without initial rounding.
1
With initial rounding. The ramp-up/down time set is exceeded accordingly.
0
Non-volatile data save not activated
1
The setpoint for the motorized potentiometer is saved in a non-volatile fashion (for p2230.0 = 1)
0
Ramp-up encoder inactive with pulse inhibit.
1
The ramp-up encoder is calculated independently of the pulse enable.
Old value is kept
0 0
Tec_ctr mop befRFG [%]
0 1
1 0
1 1
Missing enable sig
3
4
<2>
Tec_ctr mop t_r-up
0.0 ... 1000.0 [s]
p2247 [D] (10.0)
y
p2237
p2237
r2245
x
-p2238
r0046
1 = OFF1, enable missing
r0046
.0
Tec_ctrl mop mem [%]
5
fp_7954_97_61.vsd
13.03.2018
<2>
Tec_ctrMop t_rdown
0.0 ... 1000.0 [s]
p2248 [D] (10.0)
Tec_ctr mop aftRFG [%]
y
r2250
x
y = 0
Tec_ctrl mop start
-200.00 ... 200.00 [%]
p2240 [D] (0.00)
<1>
r2231
6
7
Function diagram
G120 CU230P-2
V4.7_10
8
- 7954 -

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Cu230p-2Cu230p-2 hvacCu230p-2 btCu230p-2 dpCu230p-2 pnCu230p-2 can

Table des Matières