Siemens SINAMICS G120 Mode D'emploi page 619

Masquer les pouces Voir aussi pour SINAMICS G120:
Table des Matières

Publicité

PZD send word
PZD send word
PZD send word
PZD send word
PZD send word
PZD send word
PZD send word
PZD send word
<1>
The send word 1 must be used as status word (ZSW1).
<2>
The preconfiguration with the speed setpoint is set automatically via p1000 = 6.
<3>
Physical word values are inserted in the telegram as referenced variables. p200x apply as reference variables (telegram contents = 4000 hex,
if the input variable has the value p200x).
The following applies for temperature values: 100° C -> 100 % = 4000 hex; 0° C -> 0%.
1
2
Fieldbus Interface (USS, Modbus, BACnet)
Send telegram, free interconnection via BICO (p0922 = 999)
Diag send word
r2053[0 ... 7]
p2051[0]
<1>
...
(2089[0])
p2051[1]
(2089[0])
p2051[2]
(2089[0])
p2051[3]
(2089[0])
p2051[4]
(2089[0])
p2051[5]
(2089[0])
p2051[6]
(2089[0])
p2051[7]
(2089[0])
<3>
Reference quantities for
further interconnection
p200x
3
4
PZD send word 1
<1>
PZD send word 2
<2>
PZD send word 3
PZD send word 4
Send telegram
PZD send word 5
PZD send word 6
Fieldbus
PZD send word 7
PZD send word 8
5
6
Function diagram
fp_9370_97_62.vsd
CU230P-2 BT/HVAC
13.03.2018
V4.7_10
7
8
- 9370 -