Operating Instructions
7 Operation and parameter settings
7.1 Initialization
Once the voltage supply has been connected, all segments on the display light up for 2 seconds in the
primary color, then 2 seconds in the warning color to check all segments are functioning correctly. The follow-
ing indications are then displayed for 2 seconds:
Display area A: "SICK"
•
Display area B: "PAC50" or "PAC50-LT" with variant PAC50-FGG
•
Display areas C2 and E2: "Firmware version"
•
The device then enters display mode.
7.2 In operation: display mode
The measuring and switching functions are in operation.
The device has an energy-saving mode which switches off the display ("DISC" function). In energy-saving
•
mode (DISC: OFF), the display is briefly reactivated (10 seconds) when one of the pushbuttons is pressed.
7.3 Info mode
Pressing the
pushbutton for a longer period (> 3 seconds) displays the following parameters consecutively
for 3 seconds each (see "Parameter info" in Section 2). Subsequently, the device switches back to display
mode:
SP1/FH1
(settings for switching point 1/upper window limit 1)
•
RP1/FL1
(settings for reset point 1/lower window limit 1)
•
SP2/FH2
(settings for switching point 2/upper window limit 2)
•
RP2/FL2
(settings for reset point 2/lower window limit 2)
•
Analog output
(electrical output signal in mA or V)
•
LOW
(minimum applied pressure value that has been stored since the last reset)
•
HIGH
(maximum applied pressure value that has been stored since the last reset)
•
8 8
O p e r a t i n g I n s t r u c t i o n s | S I C K
Operation and parameter settings
8017612/14NK / 8/2/2019 | PAC50
Subject to change without notice
PAC50