Operating Instructions
8.3 Behavior of the analog output in the event of an error
I / mA
20,5
20,0
4,0
3,8
I / mA
20,5
20,0
4,0
3,8
UL
Lower limit of measuring range
Figure 18: Behavior of the analog output in the event of an error (1)
Current output according to the applicable range as per NAMUR NE43: max. output current 20.5 mA/min. output current 3.8 mA.
The transition between the linear range LLR...ULR...OL can be unsteady in the range between ULR and OL. (The same applies to UL...LLR.)
8017612/14NK / 8/2/2019 | PAC50
Subject to change without notice
Errors
Analog output
4 mA ... 20 mA
(normal function)
Analog output
4 mA ... 20 mA
(inverted mode)
 20 mA ... 4 mA