Operation And Parameter Settings - SICK PAC50 Notice D'instruction

Masquer les pouces Voir aussi pour PAC50:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Operating Instructions

7 Operation and parameter settings

7.1 Initialization
Once the power supply has been connected, all segments on the display light up for 2 seconds in the primary
color, then 2 seconds in the warning color to check all segments are functioning correctly. The following
indications are then displayed for 2 seconds:
Display area A: "SICK"
Display area B: "PAC50"
Display areas C2 and E2: "Firmware revision"
The device then enters display mode.
7.2 In operation: Display mode
The measuring and switching functions are in operation.
The device has an energy-saving mode which switches off the display ("DISC" function). In energy-saving
mode (DISC: OFF), the display is briefly reactivated (10 seconds) when one of the pushbuttons is pressed.
7.3 Info mode
Pressing the pushbutton for a longer period (> 3 s)
seconds each (see "Parameter info" in Section 2). The device returns to display mode subsequently:
SP1/FH1
(Settings for switching point 1/upper window limit 1)
RP1/FL1
(Settings for reset point 1/lower window limit 1)
SP2/FH2
(Settings for switching point 2/upper window limit 2)
RP2/FL2
(Settings for reset point 2/lower window limit 2)
Analog output
(electrical output signal in mA or V)
LOW
(minimum applied pressure value that has been stored since the last reset)
HIGH
(maximum applied pressure value that has been stored since the last reset)
Return to display mode by pressing the buttons
.
8017612/YSZ4/2016-02-09 | PAC50
Subject to change without notice
7 Operation and parameter settings
displays the following parameters consecutively for 3
and
simultaneously or by pressing the middle button
O p e r a t i n g I n s t r u c t i o n s | S I C K
PAC50
6 5

Publicité

Table des Matières
loading

Table des Matières