Errors - SICK PAC50 Notice D'instruction

Capteur de pression
Masquer les pouces Voir aussi pour PAC50:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Operating Instructions

8 Errors

8.1 Errors and warning messages (indicator flashes in display segments A and B, Table 5)
Indicator A
Indicator B
OL
OVERPRESS
UL
UNDERPRES
ERR1
GEN.ERROR
ERR2
SHORTOUT1
SHORTOUT2
ERR3
OVERVOLTG
ERR4
LOW VOLTG
ATT1
SHIFT RP1
SHIFT RP2
ATT2
ADJ>LIMIT
KEYLOCKED
LOCK
Table 7: Errors and warning messages
9 8
O p e r a t i n g I n s t r u c t i o n s | S I C K
Status
Description
Error
Applied pressure > upper limit of measuring range
Error
Applied pressure < lower limit of measuring range
Error
General error
Error
Short-circuit at one of the two outputs
Error
Applied supply voltage > 30 V DC
Error
Applied supply voltage < 17 V DC
Warning
Switching point setting made by the operator below
the reset point that is set. The reset point is auto-
matically set below the new switching point with the
smallest possible hysteresis.
Warning
Displayed if the applied pressure during zero
balancing lies outside the permitted limit of 5% of
the range
Warning
Displayed if an attempt is made to access the
programming mode while the input lock is active
Errors
Action required
Set pressure to within
measuring range
Set pressure to within
measuring range
Contact SICK
Remove the short-circuit
Make the correct setting for
the supply voltage
Make the correct setting for
the supply voltage
Acknowledge by pressing the
<enter> pushbutton
Acknowledge by pressing the
<enter> pushbutton
Enter the password or unlock
via IO-Link if parameter entry
has been locked by IO-Link
8017612/14NK / 8/2/2019 | PAC50
Subject to change without notice
PAC50

Publicité

Table des Matières
loading

Table des Matières