Operating Instructions
9 Technical data
9.1 Features
Medium
Compressed air quality
Zero balancing
Measuring ranges
Process temperature
Switching outputs
Diagnostic output
8017612/14NK / 8/2/2019 | PAC50
Subject to change without notice
Technical data
Dry compressed air
According to ISO 8573-1:2010
Max. particle size: ≤ 40 μm
Oil content: 0–40 mg/m
3
The pressure dew point must be at least 15 °C below the ambient and medium tem-
perature and must be max. 3 °C.
Max. 5% of the range
–1 bar ... 0 bar; –1 bar ... +1 bar; 0 bar ... +6 bar; 0 bar ... +10 bar; –1 ... 10 bar
0 °C ... 60 °C
1 or 2 transistor switching outputs depending on the variant
PNP/NPN/push-pull can be set (in variant with IO-Link: switching output 1: option of
switching between IO-Link/PNP, and switching output 2: between PNP/NPN/push-pull)
Function: normally open/normally closed, window and hysteresis function freely adjust-
able
Switching voltage: supply voltage L
Max. switching current per switching output: 100 mA
Variants with IO-Link: IO-Link version 1.1
Switching delay: 0 s ... 50 s (programmable)
Switching time ≤ 5 ms
For variants with 2 switching outputs: switching output 2 can be used as a diagnostic
output. In the event of an error: see Table 8.2
–2 V [V DC]
+
O p e r a t i n g I n s t r u c t i o n s | S I C K
PAC50
1 0 3