8.8.1
reading the rotational frequency of
the paddle wheel
FREQUENC.
FLOW
Fig. 23 : Diagram of the "FREQUENC." parameter of the Test menu
8.8.2
monitoring the flow rate in the pipe
A malfunction in your process or of the flow sensor may be indicated
either by a flow rate which is too low or too high.
The parameter "FLOW-W." makes it possible to monitor the flow
rate.
• To disable the flow rate monitoring, set W- = W+ = 0.
• To disable one of the limits, set it to 0.
To be warned when the flow rate is too low or too high, enter the
flow rate range (in the units that have been chosen in the "UNIT"
parameter of the Parameters menu), outside which the device gen-
erates a warning message, "WARN LO" or "WARN HI", and turns
the device status LED to orange.
31
38.00 hz
English
Type 8025 / SE35, battery powered
Adjustment,Commissioning
When a warning message, "WARN LO" or "WARN HI", is generated
by the device:
→
check the process.
→
if the process is not faulty, check the flow sensor condition and
clean it if necessary.
→
if the flow rate measurement is still incorrect, contact the Bürkert
retailer.
See also "If you encounter problems" in chap. 9.4