Type 8025 / SE35, battery powered
Adjustment,Commissioning
calculating the k factor of the fitting with a teach-in procedure depending on a volume ("teAch V.")
The device will use the new K factor as soon as "SAVE YES" is confirmed when leaving the Parameters menu.
K=2.850
K-FACtOR
0......9
OUtPUt
REtURN
Fig. 17 : Teach-in procedure depending on a volume
The display shows the K factor of the fitting, may it have been entered or determined by a
Teach-In procedure.
tEACh V.
FiLL END
→
Charge the pipe to fill the tank.
→
When the tank is full, confirm "FILL END":
0000.0 L
→
Enter the volume of fluid that passed in the circuit (value between 0.1 and 9999.9
tEACh F.
in the units chosen for the totalizers at the "UNIT" parameter).
→
Confirm.
K=2.916
→
Confirm the displayed value.
VALiD N/Y
→
Confirm the K factor determined through Teach-In or not.
The device calculates the K factor of the fitting and displays it.
English
25