Adjustment,Commissioning
The following table shows the response times (10% to 90%) of the filters:
Filter 0: measured flow
rate
Fig. 20 : Available filters
Filter
Response time
0
0,15 s
1
0,7 s
2
1,4 s
3
2,5 s
4
3,5 s
Filter 3
fast
Response
Filter
time
5
6 s
6
10 s
7
19 s
8
33 s
9
50 s
slow
Filter 6
English
Filter 9
28